Standard and special Electric panels for the main areas: Refrigeration, conditioning, treatment of water, powergenerators, booster set, fire-fighting.
EN12845 – UNE 23500- UNI 10779
DISRUPTIVE TECHNOLOGY WIFI COMMUNICATION EMBEDDED WEB AMAZING FEATURES COLOURFULL DISPLAY
Standards and technical regulations
Compliance with standards and technical:
regulations: EN 12845 Ed.2015 UNE 23500 Ed. 2012 / Ed. 2018 / Ed.2021 UNI 10779 Ed. 2014 CEA-4001 Sprinkler Systems UNE-EN 61439-1 Low-voltage switchgear
Electrical features and batteries: Incoming line voltage and frequency From 85Vac to 265 Vac 50-60Hz depending on model
Nominal battery voltage: 12 Vdc or 24 Vdc depending on model
Pump and system protections
Total system alarms: 42
Design features
Enclosure: IP65 Protected from total dust ingress (NEMA 4)
Impact rating: IK10 (except for display)
Fireproof grade: Fire extinguishes <30s
Display TFT colour4.3” 480x272 px
Buzzer 75 dB measured at 1m
Wiring: Halogen free Fire resistance: RZ1 according to EN50200 (830º during 90min)
Pressure transducer: 1 pressure measuring device using pressure transducers 0-100bar / 4-20mA
It can be used to monitor the system pressure of the pump
The demand pressure to start and stop the pump are configurable
Pressure Switch Monitored to prevent short-circuit or open-circuit faults
Working temperatures Recommended: -5ºC to 40ºC (tested up to 60ºC)
Relative humidity (non-condensing) Functional: 20 to 95%.
Cooling: Natural convection
Maximum altitude: 2000m
Pollution degree 2
Pump start methods
Automatic Mode: Pressure switch line: Low system pressure
Manometer: system pressure Water level contact: Low priming tank level
Remote start contact
Manual Mode “Battery A” and “Battery B” press buttons in front panel
Test Mode Manual start press button to evaluate the status of the emergency start button
Measuring instruments
Batteries: 2 voltmeters, battery voltage 2 battery charge current ammeters
Engine: Engine cooling temperature (water) Engine cooling oil temperature Oil pressure Fuel tank level Engine speed in rpm
General System: 1 Voltmeter: Supply voltage AC. Accuracy >1% 1 Manometer: System pressure (4-20mA pressure sensor required) 1 Flow Meter (manual flow input / pulse output / 4/ 20 mA sensor)
Wifi: Embedded Web access
Ethernet: Modbus / TCP-IP SCOM903 optional module not included as standard
RS485 Modbus / RTU SCOM901 optional module not included as standard
Voltage free contacts: 6 potential free double relays: 30Vdc - 0.3A
1 potential free double relay 230Vdc-10A
Thanks to the volume of purchases, TIME TECHNOLOGY INDUSTRIES enjoys a favourable position on the market and is able to offer to its customers high quality products at a very competitive price.